A generator size calculator works from what must run at once and the one machine that starts hardest. Get those two right and the generator holds its voltage when the borehole pump kicks in; get them wrong and the set stalls, or a large one burns fuel to run a few lights.
Running load and the motor start
Add the watts of everything that runs together, motors included. The tool keeps that running load at no more than 80% of the set's rating, turning watts into kVA at 0.8, so 2,500 W of loads needs about 3.9 kVA, which rounds up to a 5 kVA set. Then it checks the moment the biggest motor starts, at 3 to 6 times its running watts while the rest keep going. A 750 W pump starting at three times needs about 5 kVA at that moment too, so the same set still fits. A farm with 12 kW running and a 4 kW pump starting at five times needs about 40 kVA three phase.
Petrol, diesel and the phase
Small petrol sets suit a house for a few hours of load shedding. Diesel uses less fuel for the same output and lasts longer on long runs, so farms, shops and sites usually choose it; petrol sets above about 10 kVA are rare. A three phase set is needed for three phase motors, and the loads must be spread over the phases. The tool starts three phase at 10 kVA.
Fuel per hour, as a rule of thumb
Fuel use is estimated as litres per kVA hour of output: about 0.3 for diesel, rounded up from published charts, and about 0.5 for petrol. The tool shows it at a load share you choose and at your own running load, with a cost per hour at the fuel price in the box. A real set's figure is in its manual, and a set run lightly uses more per unit than one run near its rating.
Connecting it safely
Never plug a generator into a house socket to feed the board. It needs a changeover switch fitted by an electrician, so it cannot back feed the street. For a one off event or a planned outage, generator hire may make more sense; for quiet daily backup compare an inverter.
Frequently asked questions
Which generator runs a house through load shedding?
For lights, plugs, the fridge, TV and gate, often 5 to 8 kVA. Add the geyser or a pump and it grows quickly. Type your own loads into the tool.
How much diesel does a generator use?
Roughly 0.3 litres an hour for each kVA of output, our rule of thumb from published charts. A 10 kVA set at three quarter load uses about 2 to 2.5 litres an hour.
Why is the motor start so important?
A motor draws several times its running current for a moment. If the set cannot supply it, the voltage dips, the motor stalls and other appliances may be damaged.
Do you sell or hire generators?
No. We own no generators. Send one request with the kVA, the fuel and the place, and dealers and hire firms near you quote directly.
Read more
More tools
- Cable size calculatorLoad, length, phase and how the cable is run in: the cable size in mm² and the voltage drop out
- Breaker size calculatorAppliance watts or amps and the supply in: the current, the breaker rating and the cable usually used out
- Inverter size calculatorThe appliances that must run in an outage in: the running load, the peak when motors start and the inverter kVA out
- Battery backup calculatorLoad in watts, hours and battery type in: the kWh of battery to buy, or how long a battery lasts out
- Electricity cost calculatorAppliance watts, hours a day and the rand per kWh in: units and cost a day, a month and a year out
- Ohm's law calculatorAny two of volts, amps, ohms and watts in: the other two and the formulas used out
- Downlight calculatorRoom size, room type and the lumens of a light in: how many downlights, the layout and the spacing out